Mr. Bernard P. Orlan June 12, 2002
Indoor Air Quality Assessment Pages
P. S. 89M__________________________________ ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected seventy-nine (80) sets of real-time environmental measurements consisting of
seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the
school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 10:01 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.2 °F to 78.1 °F. Twenty-nine (29) ot
the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent
relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer
season. The outdoor temperature measurements ranged from 73.9 °F to 74.1 °F.
Relative Humidity
The relative humidity indoors ranged from 44.3 to 55.6 percent. All of the indoor measurements
for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort, 'fhe outdoor relative humidity measurements ranged from 59.9 to 60.1
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 515 ppm to 1281 ppm. All of the indoor
measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 600 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1300 ppm (background level + 700 ppm). Carbon dioxide measurements are used
as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant
respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
(7arbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHR A F guideline of 9 ppm. The outdoor CO concentrations were 1
ppm for all collected readings.
Respirable Particulates (PM2,3)
Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 34 pg/m^. The
average PM2.5 concentration for the entire school building was approximately 22 pg/m^. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 ug/m- for sensitive individuals and children. The outdoor
respirable particulate concentration measurements ranged between 79 pg/m^ to 90 g/m^ with an
average of 85 pg/m^.