Mr. Bernard P. Orlan June 7, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M_______________________________ ATC Project No. 15-19125-0297 Real-Time Environmental Measurements
ATC collected seventy-nine (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 10:50 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.6 °F to 74.7 °F. Thirty-six (36) of the indoor measurements for temperature were below and none of the measurements were above the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 73 °F to 73.1 °F.
Relative Humidity
The relative humidity indoors ranged from 47.6 to 60.1 percent. One (1) of the indoor measurements for relative humidity was above and none of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 78.6 to 79.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 546 ppm to 1346 ppm. All of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 676 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1376 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 2 ppm for all collected readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 9 pg/m^ to 22 pg/m^. The average PM2.5 concentration for the entire school building was approximately 14 pg/m^. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurement.s ranged between 90 pg-m- to 94 g/m^ with an average of 92 pg/m^.
CITY_21MC100_002864558
NYC-WTC_000369979
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000369881
ASME/BOE IAQ measurements report for P.S. 89M, May 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313797
ATC report of IAQ measurements at PS/89M school building.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313837
ATC indoor air quality measurements conducted June 10, 2002 for PS 89M per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369857
Indoor air quality report for PS/89M school, measurements collected May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394489
Indoor air quality report for PS 89M with April 26, 2002 measurements.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369254
IAQ parameters with temperature, humidity, and gas readings.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370025
ATC IAQ measurements conducted June 12, 2002 for BOE air quality evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313861
ATC indoor air quality measurements collected June 12, 2002 for a NYC school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199027
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369250
ATC IAQ measurements collected June 7, 2002 for school building evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392864
ATC report of IAQ measurements at PS 89M requested by BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000369238
ATC IAQ measurements conducted June 6, 2002 for BOE evaluation.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313797
ATC report of IAQ measurements at PS/89M school building.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369254
IAQ parameters with temperature, humidity, and gas readings.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000210984
Report of indoor air quality measurements conducted at P.S. 89M on May 22, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313700
IAQ measurements for PS 89M on May 21, 2002, per BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199027
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 22, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000369881
ASME/BOE IAQ measurements report for P.S. 89M, May 24, 2002.
Similar indexed content
NYC-WTC_000313797
ATC report of IAQ measurements at PS/89M school building.
Similar indexed content
NYC-WTC_000313837
ATC indoor air quality measurements conducted June 10, 2002 for PS 89M per BOE request.
Similar indexed content
NYC-WTC_000369857
Indoor air quality report for PS/89M school, measurements collected May 22, 2002.
Similar indexed content
NYC-WTC_000394489
Indoor air quality report for PS 89M with April 26, 2002 measurements.
Similar indexed content