NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 12, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
Tl^OC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO , CO2 and TVOCs were below applicable standards and guidelines.
2. Twenty-nine (29) of the indoor measurements for temperature were below the range of 73 to
79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992
during the summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 p-g/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and
children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext 211 or
212.
Sincerely, Reviewed by;
4 TC ASSOCIA TES INC.
■ t ■, 1... z''
/ ' '' /
Yiannis Efstathiou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_2IMCl00_002863370
NYC-WTC_000369257
OCR can misread numbers and units. Confirm readings against the page image before using them.