NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality, ATC, Feb 2002

Machine-extracted title · confidence 37%

Indoor air quality evaluation at P.S. 89M, Feb 2002.

NYC-WTC_000382559–000382562
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 6, 2002 Indoor Air Quality Assessment Page 4 P S SQM ATC Project No. 15-19125-0297 below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration averaged 23 pg/m^ (A.M.) and 10 pg/m^ (P.M.).

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOCConcentr^ti^

TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.

OBSERVATIONS

During this assessment, ATC noted the following:

• The interior of the building appeared clean and free of dust and debris; • The school was partially occupied (I.S. 89) at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Respirable particulate, CO2, CO and TVOC concentrations were within applicable guidelines; 2. Eleven (11) measurements of temperature in the morning and four (4) measurements in the afternoon were below the recommended range; 3. All indoor measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 26101-212. .

Sincerely, Reviewed by: A TCASSOCIA TES INC.

Andreas C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_000466545 NYC-WTC_000382562

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000382562Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →