Mr. Bernard P. Orlan Indoor Air Qu al i ty Asses sm ent Page 4 P. S. 89M ATC Project No. 15-19125-0297 below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration averaged 23 pig/m3 (A.M.) and 10 pg/m3 (P.M.).

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hGur average.

TVOC Concentruiion

TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.

OBSERVATIONS

During this assessment, ATG noted the following:

• The interior of the building appeared clean and free of dust and debris; • The school was partially occupied (I.S. 89) at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Respirable particulate, CO2, CO and TVOC concentrations were within applicable guidelines; 2. Eleven (11) measurements of temperature in the morning and four (4) measurements in the afternoon were below the recommended range; 3. All indoor measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or2I2. t •

Sincerely, Reviewed by: A TC ASSOCIA TES INC.

Andreas G. Andreou James R. Cohn, CIH, GSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_003270797

NYC-WTC_000327353

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000327353Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →