02/08/2002 14:02 FAX 212 353 8306 ATC @003
Mr. Bernard P. Orlan February 8, 2002 Indoor Air Quality Assessment Page 2 P. S. 89M________________ _ ATC Project No. 15-19125-0297
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inlierent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. Por the real-tiine data collected, ATC uses the commonly accepted guidelines cited in tlie following publications:
Veniilation for Acceptable Indoor Air Quality (ASHRAE 62-J999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); TTiertnal Environfiiental Conditions for Hiirnaf} Occupancy (ASHRAE SS-J992); Industrial Hygienists Guide to Indoor Air Qitality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during tliis investigation- Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLEI TARGET GUIDELINES FOR UNUOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide »«WWg <700 parts per million (ppm) ASHRAE 62 BE (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) 65 micrograms per cubic meter USEPA NPAAQS Respirable of air (pg 'm^) 24-hour average Particulates (PM?,;) 40 24-hour average USEPA - recommendation for children/sensitive individuals Temperature Summer: at 50% RH ASHRAE 55 Winter; 68-75=F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AII-IA (TVOC) USEPA = United Slates Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA - American Industrial Hygiene Association
CITY_21MC100_009253153 NYC-WTC_000359853
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000359840
ATC memo detailing IAQ testing for NYC Board of Education project.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000209133
ATC Associates formal letter submitting indoor air quality measurement reports for P.S. 89M to the Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359788
ATC IAQ measurements for PS 150M, Feb 2002.
10 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359796
Memo re: PS 89M IAQ measurements and project details.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000209128
ATC Associates formal letter submitting indoor air quality measurement reports for P.S. 89M to the Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000340627
ATC May 16, 2002 memo re IAQ measurements at PS 89M.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359918
IAQ report from ATC for PS 89M; date February 2002 noted.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382575
Indoor air quality measurements collected Feb 7, 2002 at P.S. 89M.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359820
ATC report detailing indoor air quality measurements at PS 89M.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000340699
ATC IAQ measurements conducted May 2, 2002 for P.S. 89M, NYC DOE.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000360054
ATC Indoor Air Quality report for April 2002 measurements at P.S. 89M, NYC.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000360230
ATC memo/letter transmitting IAQ measurements for PS 89M, March 2002.
12 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000359637
ATC memo re: IAQ report for PS 89M, Warren Street.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359820
ATC report detailing indoor air quality measurements at PS 89M.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359918
IAQ report from ATC for PS 89M; date February 2002 noted.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373529
Indoor air quality report for P.S. 234M, January 22, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000209133
ATC Associates formal letter submitting indoor air quality measurement reports for P.S. 89M to the Board of Education.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377122
Memo reporting indoor air quality measurements at a school site.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000359840
ATC memo detailing IAQ testing for NYC Board of Education project.
Similar indexed content
NYC-WTC_000209133
ATC Associates formal letter submitting indoor air quality measurement reports for P.S. 89M to the Board of Education.
Similar indexed content
NYC-WTC_000359788
ATC IAQ measurements for PS 150M, Feb 2002.
Similar indexed content
NYC-WTC_000359796
Memo re: PS 89M IAQ measurements and project details.
Similar indexed content
NYC-WTC_000209128
ATC Associates formal letter submitting indoor air quality measurement reports for P.S. 89M to the Board of Education.
Similar indexed content