NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan January 31, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M______________ ___ ArcPiRi.ectNoM5J9125-()2^

Real-Time Environmental Measurements

ATC collected eiglity-two (82) sets of real-time environmental measurements consisting of ten (10) outdoors and forty-two (42) inside in the morning (A.M.) and twenty-two (22) inside and eight (8) outside in the afternoon (P.M.). All five floors of the school were surveyed. These results are described below.

Field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 4:00 P.M.

Tempei'ature

Indoor dry bulb temperature measurements ranged from 68.3°F to 72.2“F (A.M.) and 64.8°F to 7].0°F. Two (2) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These were readings on the ]St floor. The average outdoor temperature was 40.0°F (A.M.)and45.6°F(P.M.).

Relative Humidi^

The relative humidity indoors ranged from 25.7 to 38.1 percent (A.M.) and 30.7 to 44.6 percent (P.M.). Four (4) readings in the morning were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity averaged 55.3 percent (A.M.) and 47.7 percent (P.M.).

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 513 to 1390 ppm (A.M.) and 549 to 999 ppm (P.M.). Two (2) of the morning COy measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations averaged 484 ppm (A.M.) and 500 ppm (P.M.). Therefore, the maximum acceptable level of CO2 at this location was 1200 ppm (background level + 700 ppm). The highest indoor level was measured in classroom 506 which it was occupied by approximately 28 individuals. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The 2"*^ and 3’"'^ floors of the school building were not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the ASHR.AE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm (A.M.) and 0 ppm (P.M.).

CITY_21MC100_009252S93

NYC-WTC_000359595

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359595Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →