Memo: Indoor air quality report, PS 89M, Jun 2002

Machine-extracted title · confidence 32%

ATC report to BOE on indoor air quality at P.S. 89M, Warren Street, Jun 2002.

NYC-WTC_000340461–000340464
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

06/18/2002 09:50 FAX 212 353 8306 •ATC @004 11 p Mr. Bernard P. Orlan June IS, 20ft? Indoor Air Quality Assessment Pages P. S. S9M ATC Project No. 15-19125-0297

Real-time KNviRONMEWTAL MsAaTOEMENTS

ATC collected scvraiiy-ntnc (SO) sets of real-time enviranmcntal measuremeots consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school, building were surveyed. These results are drsnrihed below.

Field data sheets are found in Attadunent 1, Readings began at S;00 A-M, and concluded at approximately 10:40 A-M.

Tsmperature

.Indoor dry bulb tempensture measurements ranged from 71.6 T to 73-9 °F. Forty-fnur (44) of the indoor measurements for temperature were below die range of 73 to 79°? (at 50 percent relative humidity) as recomnenned by the ASHRAE Standard 55-1997 during the summer season. The outdoor tempnature measurements ranged from 74.7 "F to 74.9 ®F.

Relative Humidity

The relative humidity indoors ranged fram 42.3 to 49.9 percent. AH of the indoor rncasurements for relative humidily were wirlrn the ASHRAE-rcoonanended range of 30 to 60 percent for occupant comfort. The outdoor relative humidily measurement.^ ranged from 49.2 to 49.4 percent.

Ctithon Dinxide Concentraiien

Carbon dioxide concenliations indoors rmrgcd from 510 ppm to 1279 ppm. AM of the indoor meaBuretnsntg for CO2 were within th.e ASHRAE Standard 62-1999 Tcrnmnicnded maximum ooncenttation of <700 ppm above the background level, The msTrirnum outdoor (background) CO2 coacentrstifm was 588 ppm. Therefore; the maximum acceptable level of COo tliis location ■wns 1288 ppm (background level + 700 ppm)- Carbon cioxida moasurements arc used as an indicator of available outside makeup air. The primary source of 002 indoors is oceupant respiration. The school building was orampied during ATC’e sssessmetit.

Carbon Monoxide Conceiaradan

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations wc-o below Ilie NPAAOS/ASHRAE guideline of 9 ppm. The outdoor CO concemratinn were 1 ITpm for oil collected readings.

Renpirable Particulates!

Respirable particulate concentrations* indoors ranged between 11 ng/m^ to 32 pf/m^. The avorngc PM2.5 concentration for the entire school building was approximately 20 pg/m^. None nf the indoor measnrenjcnta were above the NPAAQS of 65 pg/m^ 24-b.our average concentration of particulate, matter 2-5 micrometers or less in aerodynamic diameter or above the USEPA reoommendf’rt rnncentration of 40 pg/m- for sensitive individuals and children. The

CITY_21MC100_009261462 NYC-WTC_000340463

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340463Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →