08/24/2002 11:04 FAX 212 353 8306 ATC @004/014

Mr. Bernard P. Orlan June 24, 2002 Indoor Air Quality Assessment Pages P. S. S9M ATC Project No. 15-19125-0297

Real-Time Enveronmentax. Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets arc found in Attachment 1. Readings began at 8:00 A-M. and concluded at approximately 11 ;00 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 67.6 °F to 72.0 °F- All of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 diulng the summer season. The outdoor temperature measurements ranged from 70.2 °F to 70.4 °F.

Relative Humidity

The relative humidity indoors ranged from 50.5 to 59.1 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort, The outdoor relative humidity measurements ranged from 68 1 to 68.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 561 ppm to 1223 ppm. AU of the indoor measurements for CO? were within the ASHRAE Standard 62-1999 recommended maximmn concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 571 ppin. Therefore, the maximum acceptable level of CO2 at this location was 1271 ppm. (backgroimd level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. Tire school building was occupied during ATC’9 assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were also 1 ppm for all collected readings.

Respirable Particulates. (PM2.S)

Respirable particulate concentrations* indoors ranged between 15 P-g/m^ to 32 |Ug/m^. The average PM2.5 concentration for the entire school building was approximately 23 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/ni? 24>hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The

CITY_21MC100_012158178 NYC-WTC_000340439

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340439Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →