Memo: Indoor air quality report, PS 89M, Jun 2002

Machine-extracted title · confidence 32%

ATC report to BOE on indoor air quality at P.S. 89M, Warren Street, Jun 2002.

NYC-WTC_000340461–000340464
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

06/18/2002. 09:50 FAX 212 353 8306 ATC @005

Mr. Bernard P. Orlan June 18, 7.(102 Indoor Ail Quality Assessment Page 4 .P. S. 89M ATC ProieotNo. 15-19125-0297 outdoor respirable particulate concentration measurements ranged between 48 [ig/m^ to 52 g/m^ with an average of 28 ng/m^,

* The measurements made during this assessment were insiunUrcous readings, the NPAAQS is a 24-houj average,

TKQC Coneen/ratipn,!

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor 'fVOC concentration was also 0.0 ppm.

observations

During this asscKnrmt. ATC noted tire following; » The school building was occupied at the time of the assessment. ♦ No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS Based on the real-time mcasurcmcnte, tb.e following findings are presented; 1. Concenfmtions of CO and TVOCs were below applicable standards and, guidr-Hnes, n 2. Forty-four (44) of the indoor measurements for temperature werr brlnw the range of 73 to 79’F (at 50 percent relative humidity) as reconunendjcd by the ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recemmended nvi.xiinuni concentreti on of <700 ppm above die background level. 4. AH nf the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 5, None of the indoor measurements for PM2.5 were ahovr thr NPAAQS of 65 24-hour average concentration of particulate matter 2.3 ininrnm.eters or loss in aerodynamic diameter or above the USEPA recommended concentration of 40 ng/m^ for sensitive individuals and chilirer.,

It is mir plrnsurc to provide these indoor air quality aervicss to the New York City Board of EAication, Jf you have any questions about this report, please r^l (212) 353-8280, ext 211 or 212.

Sincerely, Reviewed by; ATCAfiflOCTATESlNC ..-t/

iannis Efstathkl^^ James R. Cohn, CIS, CSP Senior Project Manager Regional Manager I In.dusTrial Hygierr, T>i vision AttBohaient

J

CITY_21MC100_009261463 NYC-WTC_000340464

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340464Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →