NYC 9/11 Public Portal Document

06/21/2002 14:27 FAX 212 353 8306 ATC @005

Mr, Bernard P. Orlan June 21, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATCProiectNo. 15-19125-0297 pg/in3 for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged between 201 pg/m^ to 207 g/m^ with an average of 205 pg/m-.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

Type Concemrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • Tire school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS Based on the real-time measurements, the following findings are presented: 1. Concentrations of CO and TVOCs were within applicable standards and guidelines. 2, All of the indoor measurements for temperature were below the range of 73 to 79®F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. 4. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 5. Five (5) of the indoor measurements for PM2.5 were above the NFAAQS of 65 ug/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Twelve (12) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide dies® indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext 211 or 212.

Sincerely, Reviewed by: ATC ASSOCIATES INC,

Yiannis Efstathiou James R. Colm, ClH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attacliment

CITY_21MC100_009253052 NYC-WTC_000359687

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359687Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →