BOE requested IAQ measurements at PS 89M to evaluate school building air quality.

NYC-WTC_000411226–000411229
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

, Mr. Bernard P. Orlan June 25, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297 . sensitive individuals and children. The outdoor respirable particulate concentration measuremenls ranged between 128 (xg/m^ to 140 g/m^ with an average of 137 (xg/i'm3.

* The measurements made during this assessment were instantaneous readings, tlie NPAAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS Based on the real-time measurements, the following findings are presented: 1. Concentrations of CO and TVOCs were within applicable standards and guidelines . 2, Thirteen (13) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. , 3. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. 4. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 5. None of the indoor measurements for PM2 5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Five (5) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you ,have any questions about this report, please call (212) 353-8280, ext 211 or 212.

Sincerely, A TC ASSOCIA TES INC.

4^ Yiannis Efstathion Senior Project Manager

Attachment

CONFIDENTIAL, CITY_21MC100_003488665 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000411229

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000411229Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →