Mr. Bernard P. Orlan February 28, 2002 Indoor Air Quality' Assessment Page 3 H.S. for Leadershm & Pub. Service (M894) ATC Project No. 15-19125-0290

Real-Time Environiviental Measurements

ATC collected one hundred and forty-one (141) sets of real-time environmental measurements consisting of one hundred and thirty-six (136) in the school building and five (5) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8; 17 A.M. and concluded after 1:43 P.M. The results are described below.

TemperMure

Indoor dry bulb temperature measurements ranged from 66.8°F to 74.9°F. Ten (10) were below the range of 68 to 75°F (at 50 percent relative humidity') recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 4T7°F to 54.5'T.

Relative Humidity

The relative humidity indoors ranged from 29 percent to 30.8 percent. 24 readings were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity' range was 28.6 to 40 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 375 ppm to 1064 ppm. None of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations ranged from 332 ppm to 599 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1108 ppm (background level + 700 ppm). The highest reading was recorded m Room 515 at around 1:03 P.M. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1-2 ppm. These concentrations were below the NP;AAQS'ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2-4 ppm.

Respirable Particulates (PM2,5)

Respirable parliculate concentrations* indoors ranged between 2 pg/m^ to 37 pg/m^ with an average 9 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations ranged from 51 pg/m^ to 95 pg/m3 with an average of 66 ug/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC1OO_OO3O59O67

NYC-WTC_000335552

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335552Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370407

ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.

Similar indexed content

NYC-WTC_000370422

Indoor air quality measurements collected March 6, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →