Indoor air quality report, PS 89M, Jan 2002

Machine-extracted title · confidence 27%

IAQ measurements report for PS 89M, January 2002.

NYC-WTC_000325976–000325979
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

r real-time environmental Measurements

ATC collected ten (10) sets of real-time environmental measuremeirts consisting of seven (7) from the l®t floor of the school building and three, (3) outdoors from the playground as per the request ofthe Parents associations environmental consultant. These results are described below; The field data sheet is found in Attachment 1.

Temperature

Indoor dry bulb temperature measurements ranged trom 68.9 °F to 70.9 °F, AlTmeasurements ; were within the range of 68 to VS^F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected from 5th floor. The outdoor temperature measurements at the playground ranged fi'om 49.6 xo 49.9 °F. \ y2 A

Relative Humidity

The relative humidity indoors ranged from 38.1 percent to 39.5 percent. All measurements were within the ASHRAE-recommended range of30 to 60 percent for occupant comfoit. The outdoor relative humidity ranged from 47.9 to 48.3 percent.

CaHon DirjviiJe Concentration

Carbon dioxide concentrations indoors ranged from 402 ppm to 510 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recomniended maximum concentration of <700 ppm above the background level. The outdoor (background) GO2 concentrations were 482, 492 and 503 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1203 ppm (background level + 700 ppm). Levels above the-recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied. A3

Carbon Monoxide Concentration

Garbon monoxide concentrations indoors were 0 - 1 ppm for all readings. These concentrations were below the NPAAQS/ASHKAE guideline of 9 ppm. The outdoor CO concentration was 2 - 3 ppm. 2 2 / ■ .

Respirable Particulates

Respirable particulate concentrations* indoors ranged between 30 pg/m^ to 60 pg/m3. AH measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentration ranged from 80 - 82 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is

CITY_21MC100_003270063

NYC-WTC_000325978

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000325978Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →