Real-Time Environmental Measurements
ATC collected sixty-one (61) sets of real-time environmental measurements consisting of sixty
(60) in the school building and one (1) outdoors. All five floors of the school were surveyed.
These results are described below. Field data sheets are found in Attachment 1.
Temperature
Indoor dry bulb temperature measurements ranged from 68.3 °F to 92.0 °F. Seven (7)
measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected from floor. The outdoor temperature was 56.5 °F.
Relative Humidity
The relative humidity indoors ranged from 19.5 percent to 29.7 percent. All measurements were
below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity was 18.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 416 ppm to 540 ppm. All CO2
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 448 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1148 ppm (background level + 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO2 indoors is occupant respiration. The school building
during ATC’s assessment was not occupied.
CaH^n Monoxide Concentration
Carbon monoxide concentrations indoors were 1-2 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 3
ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 18 pg/m^. All
measurements were below the NPAAQS of 65 pg/m3 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
particulate concentration was 36 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hoLir average.