Indoor air quality report, P.S. 89M, Jan 2002

Machine-extracted title · confidence 95%

Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 15, 2002.

NYC-WTC_000236995–000236999
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Real-Time Environmental Measurements

ATC collected ten (10) sets of real-time environmental measurements consisting of seven (7) from the 1^1 floor of the school building and three (3) outdoors from the playground a.s per the request of the Parents associations environmental consultant. These results are described below. The field data sheet is found in Attachment 1.

Temperature

Indoor dry bulb temperature measurements ranged from 68.9.°F to 70.9 °F. All measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected from 5tii floor. The outdoor temperature measurements.at the playground ranged from 49.6 to 49.9 °F.

Relative Humidily

The relative huraidity indoors ranged from 38.1 percent to 39.5 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 47.9 to 48.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 402 ppm to 510 ppm. All COg measurements w'ere below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 482, 492.and 503 ppm. Therefore, the maximum acceptable level of COg at this location was 1203 ppm (background level -t 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Carbon Adonoxide Concentratioi'i

Carbon monoxide concentrations indoors were 0 - 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 - 3 ppm.

Respirable Particulates (PM2,§)

Respirable particulate concentrations* indoors ranged between 30 ug/m^ to 60 pg/m^. All measurements were below the NPAAQS of 65 pg/ui^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentration ranged from 80 - 82 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is

CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21 MC100_014659998

NYC-WTC_000236997

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000236997Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →