The assessment was performed consistent with generally accepted indoor air quality assessment
practices. As with all such assessments, there were inherent limitations created by constraints of
time, operational and work practice variability, variations in indoor air quality parameters and
sampling and analytical accuracy. Tire results of the sampling represent conditions found on the
dates of the survey and may not represent conditions found at other times. The infonnation
presented in this report should be used by the BOE as a guide to assess the need for further
improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
.such a.s offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-J999f, American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environniental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this.investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
wi ll be achieved at all times.
TABLEI
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
P\R.\M .ILK I \R<;i r I M.E aiii iscy OR
____________________________ I I i KMZA noN
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2) above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO) USEPA NPAAQS)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2.5) of air (pg/m3) 24-hour average
Temperature Summer: 73-79°F at 50% RH ASHRAE55
Winter: 68-75°F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
Total Volatile 1 ppm
Organic Compounds AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association
CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21 MC100_014659997
NYC-WTC_000236996