Real-Time Environmental Measurements
ATC collected ten (10) sets of real-time environmental measurements consisting of seven (7)
from the 1 st floor of the school building and three (3) outdoors from the playground as per the
request of the Parents associations environmenta! consultant. These results are described below.
The field data sheet is found in Attachment 1.
Temperature
Indoor dry bulb temperature measurements ranged from 68.9 °F to 70.9 °F. All measurements
were within the range of 68 to 75°F (at 50 percent relative humidity) recommended byASHRAE
Standard 55-1992 during the heating season (wintertime conditions). These measurements were
collected from 5^11 floor. The outdoor temperature measurements at the playground ranged from
49.6 to 49.9 °F.
Retative Humidity
The relative humidity indoors ranged from 38.1 percent to 39.5 percent. All measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Tire outdoor
relative humidity ranged from 47.9 to 48.3 percent.
Carbon Dioxide ConcentredioR
Carbon dioxide concentrations indoors ranged from 402 ppm to 510 ppm. All COy
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) COy
concentrations were 482, 492 and 503 ppm. Therefore, the maximum acceptable level of COy at
this location was 1203 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of COy indoors is occupant respiration. The school
building during ATC’s assessment was not occupied.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 - 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 -
3 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 30 gg/m^ to 60 gg/m^. All
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
particulate concentration ranged from 80 - 82 pg/ra^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is