Indoor air quality report, PS 89M classroom

Machine-extracted title · confidence 28%

Indoor air quality measurements at PS 89M, Jan 2002, school environment.

NYC-WTC_000325964–000325967
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

.; Real-Time Environmental MEAStiREMENTS. ■

ATC collected six^-one (61) sets of real-time environmehfal measurements consisting of sixty (60) in the school building and one (1) outdoors . All five floors of the school were surveyed . These results are described below, field data sheets are found in Attachment 1.

Temperature

Indoor dry bulb temperature measurements ranged from 68.3 °F to 92.0 °F. Seven (7) measurements were above the range of 68 to 75°F. (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected &om 5:^ floor. The outdoor temperature was 56.5 °F.

Relative Humidity

The relative humidity indoors ranged from 19.5 percent to 29.7 percent. All measurements were below' the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 18.8 percent.

Carbon Dioxide Concentrdtidn

Garbon dioxide concentrations indoors ranged from 416 ppm to 540 ppm. All GO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 448 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1148 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available G outdoor air. The primary source of COp indoors is occupant respiration. The school building during ATC’s assessmentwas not occupied. '

Cai±^Monoxide ConeenTation

Garbon monoxide concentrations indoors were 1-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor GG concentration was 3 'PP’T'

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 18 pg/m^. All measurements were below the NPAAQS of 65 pg/ni^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentration was 36 pg/mA

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-houf average.

CITY_21MC100_003270050

NYC-WTC_000325966

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000325966Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →