The assessment was performed consistent with generally accepted indoorlair quality assessment practices. As with all such assessments, there were inherent liniitations crecited by constraints of lime, operational and work practice variability,rvariations in indoor air quality parameters and sampling and analytical aceuraey. The results of tlre sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in tliis report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality iASHRAE 62-1999), Am erican Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Jduman Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, sonie^ or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

lARGLTLlAEL ____________ _ O IO\ Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) < ; / ; above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA 'nPAAQS) ..; ; , Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average Temperature Summer: 73-79°F at 5G% RH A SHRAE 55 Winter: 68-75°F at 50% RH : Relative Humidity 30 -60%; ; , if- ASHRAE 55 Total Volatile 1 ppm Organic Compounds AIHA (TVGC) / USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

CITY_21MC100_003270062

NYC-WTC_000325977

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000325977Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →