AMBIENT AIR ANO OUST SAMPUNG PROTOCOL for H.S. of Economics and Finance Page 3 of 8
Since, there are no regulatory standards for indoor air quality in non-industrial buildings, such
as offices and schools at this time, for the real-time data collected, the commonly accepted
guidelines cited in the following publications and table below shall be utilized;
Ventilation, for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industnal Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Temperature (T) Summer; 73-79“F at 50% RH ASHRAE 55
Winter 68-75°F at 50% RH
Relative Humidity (RH) 30 - 60 % ASHRAE 55
Carbon Dioxide (CO2) <700 parts per million (ppm) ASHRAE 62
above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in
(CO) ___________ ASHRAE 62)
Total Volatile Organic 1 ppm AIHA
Compounds (TVOC)
Respirable Particulates 65 micrograms per cubic USEPA NPAAQS
(PM25) meter of air (ng/m^) 24-hour
average______________ _
40 (ig/m^ 24-hour average USEPA “ Recommendation
for sensitive individuals such
as asthmatic people and
children
USEPA = United States Enviranmertal Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIWA=American tndtetriai HygieneAssociation
ASHRAE = American Society of Heating, Refrigerating, and Air-Conditioning Engineers
Results from samples collected each day shall be reported verbally, no later than 11 am the
next day, to BOE, UFT, School Principal and the PA consultant. A written report shall be
delivered or faxed by the end of the day.
In the event that real-time measurements of Temperature, Relative Humidity, and/or CO2
exceed the cited Target Guidelines, the following actions are to be taken:
1. Building engineering controls shall be adjusted and/or implemented to improve
conditions.
CITY_21MC100_003267179
NYC-WTC_000324137