AMBIENT AIR AND DUST SAMPLING PROTOCOL for H.S. of Economics and Finance Page 3 of 8
Since, there are no regulatory standards for indoor air quality in non-industrial buildings, such
as offices and schools at this time, for the real-time data collected, the commonly accepted
guidelines cited in the following publications and table below shall be utilized:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industnal Hygienists Guide to Indoor Air Quality investigations (1993), American
industrial Hygiene Association (AIHA).
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
^RAMETER
___________________ I
Temperature (T) Summer 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity (RH) 30-60% ASHRAE 55
Carbon Dioxide (CO2) <700 parts per million (ppm) ASHRAE 62
above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in
ICO)____________ ASHRAE 62)
Total Volatile Organic 1 ppm AIHA
Compounds (TVOC)
Respirable Particulates 65 micrograms per cubic USEPA NPAAQS
(PM2.5) meter of air (|ig/m^) 24-hour
average_______________
40 iig/m^ 24-hour average USEPA - Recommendation
for sensitive individuals such
as asthmatic people and
children
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = Amen'can Industrial Hygiene Association
ASHRAE = American Society of Heating, Refrigerating, and Air-Conditioning Engineers
Results from samples collected each day shall be reported verbally, no later than 11 am the
next day, to BOE, UFT, School Principal and the PA consultant. A written report shall be
delivered or faxed by the end of the day.
In the event that real-time measurements of Temperature, Relative Humidity, and/or COa
exceed the cited Target Guidelines, the following actions are to be taken:
1. Building engineering controls shall be adjusted and/or implemented to improve
conditions.