AMBIENT AIR AND DUST SAMPLING PROTOCOL for PS/IS89M. Page 3 of 8
EVALUATION CRITERIA:
Since, there are no regulatory standards for indoor air quality in non-industrial buildings, such
as offices and schools at this time, for the real-time data collected, the commonly accepted
guidelines cited in the following publications and table below shall be utilized:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER
________________ \
TARGET LEVEL
____________________ ■ ■Illi
■III
AGENCY OR
ORGANIZATION
■ ■III
Temperature (T) Summer: 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity (RH) 30-60% ASHRAE 55
Carbon Dioxide (CO2) <700 parts per million (ppm) ASHRAE 62
above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in
ICO)____________ ASHRAE 62)____________
Total Volatile Organic 1 ppm AIHA
Compounds (TVOC)
Respirable Particulates 65 micrograms per cubic USEPA NPAAQS
(PMas) meter of air (gg/m^)
USEPA = United States Environmental Protection Agency
NPAAQS = National PrimaryAmbient-Air Quality Standard
AIHA = American Industrial Hygiene Association
ASHRAE = American Society of Heating, Refrigerating, and Air-Conditioning Engineers
Results from samples collected each day shall be reported verbally, no later than Sam the
next day, to BOE, UFT, School Principal and the PA consultant. A written report shall be
delivered or faxed by the end of the day.
In the event that real-time measurements of Temperature, Relative Humidity, and/or CO2
exceed the cited Target Guidelines, the following actions are to be taken:
1. Building engineering controls shall be adjusted and/or implemented to improve
conditions.
In the event, that real-time measurements of respirable particulates exceed the cited Target
Guidelines, BOE will immediately notify the UFT. the school principal, the school custodian
and the PA consultant. The said parties will assess the situation and implement the
appropriate response action(s).