Indoor air quality memo, PS 89M, 2002

Machine-extracted title · confidence 32%

IAQ assessment update for PS 89M dated March 18, 2002.

NYC-WTC_000313369–000313373
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 19, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297 average PM2.5 concentration for the entire school building was approximately 14 ug in A All of the seventy (70) instantaneous indoor readings were below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 19 to 23 pg/m- with an average of 21 pg/m3. All outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the EPA recommended guideline for children and sensitive individuals of 40 pg/m^-

* The measurements made during this assessment were instantaneous readings, the NP.XAQS is a 24-hour average.

TVOC Concsntrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were below applicable standards and guidelines. 2. Sixteen (16) of the indoor measurements for temperature were below and fifty-four (54) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Forty-six (46) of the indoor measurements for relative humidity were below and twenty-four (24) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Four (4) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The two (2) highest readings (1213 ppm) were measured in room 404 with 28 occupants at 10:30 AM and in room 526 with 209 occupants at 11:30 AM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration.

CITY_21MC100_003047488

NYC-WTC_000313372

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313372Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

IAQ report for PS 89M, Apr 2002 · page 4

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

Similarity score 0.994 (not a probability)

machine-extracted · confidence unavailable · Check page ↗

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →