Mr. Bernard P. Orlan April 12,2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATCProiectNoJ5Jil25:T!^
The average PM2.5 concentration for the entire school building was approximately 13 pg/m^.
The outdoor respirable particulate concentration ranged from 24 to 35 pg/m^ with an average of
26 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. One (1) of the indoor measurements was below the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading was taken in room 380 (1250 ppm) at 2:20 PM with 19 occupants. Levels
above the recommended maximum do not indicate a health risk. Carbon dioxide
measurements are used as an indicator of available outdoor air. The primary source of CO2
indoors is occupant respiration.
3. Twenty-seven (27) indoor measurements for temperature were above and twenty-four (24)
were within the range of 68 to 75 °F (at 50 percent relative humidity) as recommended by
ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
4. None of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals and children.
5. Twenty-seven (27) indoor measurements for temperature were above and twenty-four (24)
were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by
ASHRAE Standard 55-1992 during the heating season (wintertime conditions).