Mr. Bernard P. Orlan April 12,2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATC Project No. 15-19125-0279

The average PM2.5 concentration for the entire school building was approximately 13 gg/m^. The outdoor respirable particulate concentration ranged from 24 to 35 pg/m^ with an average of 26 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm. OBSERVATIONS

During this assessment, ATC noted the following: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

I. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. One (1) of the indoor measurements was below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading was taken in room 380 (1250 ppm) at 2:20 PM with 19 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 3. Twenty-seven (27) indoor measurements for temperature were above and twenty-four (24) were within the range of 68 to 75 °F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. None of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. 5. Twenty-seven (27) indoor measurements for temperature were above and twenty-four (24) were within the range of 68 to 75 °F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

CITY_21MC100_0 03032222

NYC-WTC_000199190

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000199190Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →