NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 22, 2002
Indoor Air Quality Assessment Page 4
P. S. 150M ATC Project No. 15-19125-0289
respirable particulate concentration measurements ranged from 48 to 61 pg/m^ with an average
of 31 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• There was construction work going on in the plaza;
• The school building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, CO2 and TVOCs were below applicable standards and guidelines.
2. Six (6 ) of the indoor measurements for temperature were below and twenty-four (24)
measurements were within the range of 73 to 79 °F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the summer conditions.
3. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent
for occupant comfort.
4. All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65
pg/m3 for 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter. One (1) of the thirty (30) instantaneous indoor readings was above
the USEPA recommendation of 40 pg/m^ for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely, Reviewed by: _
A TC ASSOCIA TES INC.
:
^z'Amel Javm
J James R. Cohn, CIH, CSP
Senior Prdj/ct Manager Regional Manager
Industrial Hygiene Division
Attachment
CONFIDENTIAL, CITY_21MC100_005759599
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000177957