Mr. Bernard P.. Orlan March 19, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:10 A.M. and concluded al approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 61.9 °F to 71.8 °F. Sixteen (16) of the indoor measurements for temperature were below and fifty-four (54) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). Tlie outdoor temperature measurements ranged from 38.4 to 42.3 °F.

Relative Humidity

The relative humidity indoors ranged from 24.8 to 40.1 percent. Forty-six (46) of the indoor measurements for relative humidity were below and twenty-four (24) were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity- measurements ranged from 43.1 to 47.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 468 ppm to 1213 ppm. Four (4) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 445 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1145 ppm (background level + 700 ppm). The two (2) highest readings (1213 ppm) were measured in room 404 with 28 occupants at 10:30 AM and in room 526 with 209 occupants at 11:30 AM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary- source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 37 pg/m^. All of the indoor measurements for PM2.5 were below the NP/AAQS of 65 pg m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The

CITY_21MC100_003047487

NYC-WTC_000313371

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313371Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →