NYC-WTC_000400218
IAQ measurements at PS 89M for NYC BOE evaluation, March 2002.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗IAQ measurements at PS 89M for BOE evaluation, March 2002.
NYC-WTC_000400243–000400247OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 19,2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:10 A.M. and concluded at approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 61.9 "F to 71.8 °F. Sixteen (16) of the indoor measurements for temperature were below and fifty-four (54) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 38.4 to 42.3 °F.
Relative Humidity
The relative humidity indoors ranged from 24.8 to 40.1 percent. Forty-six (46) of the indoor measurements for relative humidity were below and twenty-four (24) were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 43.1 to 47.9 percent.
Carbon Dioxide Concentration .
Carbon dioxide concentrations indoors ranged from 468 ppm to 1213 ppm. Four (4) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 445 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1145 ppm (background level + 700 ppm). The two (2) highest readings (1213 ppm) were measured in room 404 with 28 occupants at 10:30 AM and in room 526 with 209 occupants at 11:30 AM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.
Respirable Particulates (PM2_s)
Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 37 pg/m^. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The
CITY_21MC100_000623826 NYC-WTC_000400245
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000400218
IAQ measurements at PS 89M for NYC BOE evaluation, March 2002.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313356
March 19, 2002 IAQ report for PS 89M site visit.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383864
ATC report of IAQ measurements collected at P.S. 89M for BOE evaluation.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397271
IAQ measurements report for PS 234M, Apr 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313369
IAQ assessment update for PS 89M dated March 18, 2002.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000222482
ATC Associates letter submitting indoor air quality measurement results collected on April 17, 2002, at P.S. 89M for the NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392768
ATC report of IAQ measurements collected May 3, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313339
ATC IAQ memo detailing measurements and scope of work at PS 89M.
15 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199187
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 234M on April 11, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392778
ATC indoor air quality measurements collected May 3, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369723
ATC IAQ measurements at PS 89M for BOE, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000383864
ATC report of IAQ measurements collected at P.S. 89M for BOE evaluation.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313356
March 19, 2002 IAQ report for PS 89M site visit.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313369
IAQ assessment update for PS 89M dated March 18, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392661
IAQ report dated April 22, 2002 for PS 89M; BOE evaluation requested.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313458
IAQ measurements at P.S. 89M; BOE evaluation, April 12, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000222495
ATC Associates letter submitting indoor air quality measurement results collected on April 19, 2002, at P.S. 89M for the NYC Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000400218
IAQ measurements at PS 89M for NYC BOE evaluation, March 2002.
Similar indexed content
NYC-WTC_000313356
March 19, 2002 IAQ report for PS 89M site visit.
Similar indexed content
NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
Similar indexed content
NYC-WTC_000383864
ATC report of IAQ measurements collected at P.S. 89M for BOE evaluation.
Similar indexed content
NYC-WTC_000397271
IAQ measurements report for PS 234M, Apr 2002.
Similar indexed content