NYC 9/11 Public Portal Document
Mr Bernard P Orlan March 1, 2002
Indoor Air Quality Assessment Page 3
H S for Leadership & Public Service (M894~> ATCProiectNo 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) m the school building and twelve (12)
outdoors All fourteen floors of the school were surveyed Field data sheets are found in the
Attachment Readings began at 11 10 AM and concluded after 7 43 P M The results are
described below
Temperature
Indoor dry bulb temperature measurements ranged from 60 9°F to 75 0°F Ten (10) were below
the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard
55-1992 during the heating season (wintertime conditions) The outdoor temperature range was
42 9°F to 58 7°F
Relative Humidity
The relative humidity indoors ranged from 18 4 percent to 42 5 percent. Eight (8) measurements
were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort All
other relative humidity measurements were below the ASRAE recommended range The
outdoor relative humidity range was 18 4 to 42 5 percent
Carbon Dioxide Concentration
Carbon dioxide concentiations indoors ranged from 423 ppm to 984 ppm None of the
measurements were above the ASHRAF Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level The outdoor (background) CO2
concentrations ranged from 267 ppm to 521 ppm Therefore, the maximum acceptable level of
CO2 at this location was 1221 ppm (background level -t- 700 ppm) Levels above the
recommended maximum do not indicate a health risk Carbon dioxide measurements are used as
an indicator of available outdoor air The primary source of CQ2 indoors is occupant respiration
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-2 ppm These concentrations were below the
NPAAQS/ASl IRAE guideline of 9 ppm The outdoor CO concentrations were 1-3 ppm
Respirable Particulates CPM2 5)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 28 pg/m^ with an
average 7 pg/m^ None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter
The outdoor respirable paniculate concentrations ranged from 18 pg/m^ to 71 pg/m^ with an
average of 44 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average