Mr Bernard P Orlan March 1,2002
Indoor Air Quality Assessment Page 4
H S foi Leadership & Public Service (M894) ATC Proiect No 15-19125-0290
TVOC Concentration
The TVOCs concentrations was 0 ppm inside the building These concentrations were below the
AIHA guideline for odor control of 1 ppm The outdoor TVOC concentration was also 0 ppm
OBSERVATIONS
During this assessment, ATC noted the following
• The interior of the building appeared clean and free of dust and debris,
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Rased on the real-time measurements, the following findings are presented
1. Concentrations of CO2, CO and TVOCs, were within applicable standards and guidelines
2, Ten (10) temperature measurements were below the range of 68 to 75°F (at 50 percent
relative humidity recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions)
3. Eight (8) of the relative humidity measurements were within the ASHRAE lecommended
range of 30 to 60 percent for occupant comfort All other measurements were below the
ASHRAE recommended range
4. None of the indoor respirable particulate measurements were above the EPA recommended
guideline for children and sensitive individuals of 40p.g/m3 Three (3) of the outdoor
readings were above the NPAAQS of 65 pg/m^ and another three (3) outdoors readings were
above the USEPA recommended guideline for sensitive individuals and children of 40
pg/m^
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education If you have any questions about this report, please call (212) 353-8280, extension
261 or2]2
Sincerely, Reviewed by
-I TC ASSOCIA TES INC.
Andreas C Andreou James R Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_006797828
NYC-WTC_000297877