Mr Bernard P Orlan March 8 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Public Service (M894~) ATCProiectNo 15 19125 0290 Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) in the school building and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 10 23 AM and concluded after 6 23 P M The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 67 8 °F to 77 2 °F One (1) indoor measurement was below and four (4) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 55 6 °F to 64 7 °F

Relative Humidity

The relative humidity indoors ranged from 23 2 percent to 58 3 percent One hundred and fifteen (115) measurements were below the ASHRAF recommended range of 30 to 60 percent for occupant comfort Thirteen (13) indoor measurements were within the ASHRAF recommended range The outdoor relative humidity range was 21 4 to 26 4 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 491 ppm to 1082 ppm All of the measurements were below the ASHRAF Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentration was 643 ppm Therefore the maximum acceptable level of CO2 at this location was 1343 ppm (background level + 700 ppm) Levels above the recommended maximum do not indicate a health nsk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 2 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations were 2 4 ppm

Respirable Particulates (PM2 §)

Respirable particulate concentrations* indoors ranged between 11 pg/m^ to 48 pg/m^ with an average 26 ug/m^ None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter Two (2) of the one hundred twenty eight (128) instantaneous measurements were above the USFPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^ The outdoor respirable particulate concentrations ranged from 64 pg/m^ to 123 pg/m^ with an average of 93 pg/m^ Fleven (11) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter All of the outdoor instantaneous measurements

CITY_21MC100_003085354

NYC-WTC_000295789

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295789Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →