March 26, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.

NYC-WTC_000295923–000295927
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 27 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Public Service fM894) ATCProiectNo 15 19125 0290 Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) in the school building and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 10 11 AM and concluded after 6 23 PM The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 71 5 °F to 78 8 °F One hundred and one (101) mdoor measurements for temperature were above and twenty seven (27) measurement were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 39 6 °F to 46 2 °F

Relative Humidity

The relative humidity indoors ranged from 26 2 percent to 39 9 percent One hundred and twenty one (121) of the indoor measurements for relative humidity were below and seven (7) measurements were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort The outdoor relative humidity range was 22 4 to 34 0 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 487 ppm to 1398 ppm One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentration was 439 ppm Therefore the maximum acceptable level of CO2 at this location was 1139 ppm (background level + 700 ppm) The highest measurement was taken in the gymnasium at 12 54 PM with one (1) occupant Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The pnmaiy source of CO2 indoors is occupant respiration

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations ranged from 2 ppm 6 ppm

Respirable Particulates (PM2 3)

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 20 pg/m^ with an average 6 pg/m- All of the mdoor measurements for PM2 5 were below the NPAAQS of 65 pg/m3 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children The outdoor respirable particulate concentrations ranged from 20 pg/m^ to 68 pg/m^ with an average of 32 pg/m^ One (1) of the outdoor measurements for PM2 5 was above the NPAAQS of 65 pg/m^ 24 hour average

CITY_21MC100_003085609

NYC-WTC_000295925

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295925Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →