NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 4 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Public Service fM894) ATC Project No 15 19125 0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) m the school building and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 11 47 A M and concluded after 9 00 P M The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 62 2 °F to 74 9°F Twenty five (25) were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 46 2 °F to 53 9 °F

Relative Humidity

The relative humidity indoors ranged from 19 8 percent to 42 1 percent One hundred and seven (107) measurements were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort Twenty four (24) indoor measurements were within the ASHRAE recommended range The outdoor relative humidity range was 20 6 to 23 2 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 436 ppm to 1139 ppm One (1) of the measurements was above the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentrations ranged from 314 ppm to 421 ppm Therefore the maximum acceptable level of CO2 at this location was 1121 ppm (background level + 700 ppm) The highest reading (1139 ppm) was found in room 905 at 12 27 PM with 33 occupants Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 3 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations were 1 5 ppm

Respirable Particulates (PM2 5)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 29 pg/m^ with an average 9 pg/m^ None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter The outdoor respirable particulate concentrations ranged from 28 pg/m^ to 84 pg/m^ with an average of 44 pg/m3

* The measurements made during this assessment were instantaneous readings the NPAAQS is a 24 hour average

CITY_21MC100_003085297

NYC-WTC_000295728

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295728Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000297874

ATC report of IAQ measurements collected on Feb 28, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →