Mr Bernard P Orlan March 15 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Public Service fM894) ATC Project No 15 19125 0290 REAL Time Environmental Measurements ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) in the school buildmg and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readmgs began at 8 06 AM and concluded after 3 37 PM The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 71 5 °F to 79 7 °F Sixteen (16) indoor measurement for temperature were within and one hundred seventy two (172) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 56 7 °F to 65 1 °F

Relative Humidity

The relative humidity indoors ranged from 29 6 percent to 43 5 percent Three (3) of the indoor measurements for relative humidity were below and one hundred eighty five (185) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort The outdoor relative humidity range was 41 4 to 48 7 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 321 ppm to 1096 ppm All of the indoor measurements for CO2 were below the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentration was 572 ppm Therefore the maximum acceptable level of CO2 at this location was 1272 ppm (background level + 700 ppm) Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The pnmary source of CO2 indoors is occupant respiration

CarbonMonpxideConcenmgti^

Carbon monoxide concentrations indoors ranged from 1 ppm to 3 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations ranged from 3 ppm 4 ppm

Respirable Particulates (PM2

Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 36 pg/m^ with an average 25 pg/m^ All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^ The outdoor respirable particulate concentrations ranged from 76 pg/m3 to 147 pg/m3 with an average of 108 pg/m3 All of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^

CITY_21MC100_0 03085452

NYC-WTC_000295868

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295868Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →