NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

Indoor air quality report, BOE school

Machine-extracted title · confidence 42%

March 2002 IAQ measurements at selected NYCBOE school for QA purposes.

NYC-WTC_000295890–000295894
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 20 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Public Service fM894) ATCProiectNo 15 19125 0290

Real Time Environmental Measurements ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) m the school building and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 7 37 A M and concluded after 3 03 P M The results are described below

Temjjerature

Indoor dry bulb temperature measurements ranged from 69 4 °F to 76 3 °F One hundred and twenty five (125) mdoor measurement for temperature were within and three (3) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 45 3 °F to 46 5 °F

Relative Humidity

The relative humidity indoors ranged from 28 4 percent to 40 4 percent Fifty nine (59) of the indoor measurements for relative humidity were below and sixty nine (69) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort The outdoor relative J humidity range was 42 7 to 45 8 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 432 ppm to 1003 ppm All of the indoor measurements for CO2 were below the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentration was 511 ppm Therefore the maximum acceptable level of CO2 at this location was 1211 ppm (background level + 700 ppm) Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations ranged from 1 ppm 4 ppm

Respirable Particulates (PM2 5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 22 pg/m^ with an average 11 pg/m^ All of the indoor measurements for PM2 5 were below the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^ The outdoor respirable particulate concentrations ranged from 44 pg/m^ to 121 pg/m^ with an average of 77 pg/m^ Eight (8) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less m aerodynamic diameter All of the twelve (12)

CITY_21MC100_003085511

NYC-WTC_000295892

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295892Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →