NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 5 2002 Indoor Air Quality Assessment Page 3 H S for Leadershin & Public Service (M894) ATCProiectNo 15 19125 0290

Real Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) in the school building and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 8 18 AM and concluded after 3 51PM The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 62 1 °F to 73 3 9°F Seven (7) were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 40 4 °F to 53 8 °F

Relative Humidity

The relative humidity indoors ranged from 19 4 percent to 42 3 percent One hundred and twenty five (125) measurements were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort Three (3) mdoor measurements were within the ASHRAE recommended range The outdoor relative humidity range was 19 4 to 24 1 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 364 ppm to 1156 ppm All of the measurements were below the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentrations ranged from 308 ppm to 581 ppm Therefore the maximum acceptable level of CO2 at this location was 1281 ppm (background level + 700 ppm) Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 2 ppm These concentrations were below the NPAAQS/ASHRAE guidelme of 9 ppm The outdoor CO concentrations were 1 3 ppm

Respirable Particulates (PM2

Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 26 pg/m^ with an average 7 pg/m^ None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter The outdoor respirable particulate concentrations ranged from 30 pg/m^ to 85 pg/m^ with an average of 55 pg/m^

* The measurements made during this assessment were instantaneous readings the NPAAQS is a 24 hour average

CITY_21MC100_003085316

NYC-WTC_000295747

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295747Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000297874

ATC report of IAQ measurements collected on Feb 28, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →