Mr Bernard P Orlan March 6 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Public Service (M894) ATC Project No 15 19125 0290
Real Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) in the school building and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 9 30 AM and concluded after 4 51 PM The results are described below
Temperature
Indoor dry bulb temperature measurements ranged from 38 7 °F to 73 4 °F Eleven (11) were below and all other readings were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 38 8 °F to 52 6 °F
Relative Humidity
The relative humidity indoors ranged from 18 1 percent to 37 3 percent One hundred and twenty four (124) measurements were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort Four (4) indoor measurements were within the ASHRAE recommended range The outdoor relative humidity range was 15 to 23 8 percent
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 313 ppm to 1340 ppm Levels above the recommended maximum do not indicate a health nsk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 3 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations were 1 5 ppm
Respirable Particulates (PM2
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 44 pg/m^ with an average 9 pg/m^ None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter This average concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^ The outdoor respirable particulate concentrations ranged from 33 pg/m^ to 91 pg/m^ with an average of 65 pg/m^
* The measurements made during this assessment were instantaneous readings the NPAAQS is a 24 hour average
CITY_21MC100_004151183
NYC-WTC_000295751
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000295745
ATC memo about IAQ measurements at a NYC school for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295726
ATC Associates memo documenting indoor air quality measurements at a NYC school.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295768
ATC report of IAQ measurements at a NYC school for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295919
March 25, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295866
ATC report on indoor air quality measurements at NYC school; March 14, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189753
Cover letter and report summary for indoor air quality measurements collected at a school on February 27, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295915
March 22, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297874
ATC report of IAQ measurements collected on Feb 28, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297826
ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297808
ATC indoor air measurements report for February 14, 2002 at the school.
10 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295792
ATC report on IAQ measurements conducted at the referenced NYC school.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297663
Indoor air quality measurements report dated Feb 5, 2002 for the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000295866
ATC report on indoor air quality measurements at NYC school; March 14, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295726
ATC Associates memo documenting indoor air quality measurements at a NYC school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295745
ATC memo about IAQ measurements at a NYC school for BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295915
March 22, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295768
ATC report of IAQ measurements at a NYC school for BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295890
March 2002 IAQ measurements at selected NYCBOE school for QA purposes.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000295745
ATC memo about IAQ measurements at a NYC school for BOE.
Similar indexed content
NYC-WTC_000295726
ATC Associates memo documenting indoor air quality measurements at a NYC school.
Similar indexed content
NYC-WTC_000295768
ATC report of IAQ measurements at a NYC school for BOE.
Similar indexed content
NYC-WTC_000295919
March 25, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
Similar indexed content
NYC-WTC_000295866
ATC report on indoor air quality measurements at NYC school; March 14, 2002.
Similar indexed content