Memo/letter: Indoor air quality, school IAQ

Machine-extracted title · confidence 50%

ATC memo describing IAQ measurements at the referenced NYC school.

NYC-WTC_000295749–000295752
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 6 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Public Service (M894) ATC Project No 15 19125 0290

Real Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real time environmental measurements consisting of one hundred and twenty eight (128) in the school building and twelve (12) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 9 30 AM and concluded after 4 51 PM The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 38 7 °F to 73 4 °F Eleven (11) were below and all other readings were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) The outdoor temperature range was 38 8 °F to 52 6 °F

Relative Humidity

The relative humidity indoors ranged from 18 1 percent to 37 3 percent One hundred and twenty four (124) measurements were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort Four (4) indoor measurements were within the ASHRAE recommended range The outdoor relative humidity range was 15 to 23 8 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 313 ppm to 1340 ppm Levels above the recommended maximum do not indicate a health nsk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 3 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations were 1 5 ppm

Respirable Particulates (PM2

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 44 pg/m^ with an average 9 pg/m^ None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter This average concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^ The outdoor respirable particulate concentrations ranged from 33 pg/m^ to 91 pg/m^ with an average of 65 pg/m^

* The measurements made during this assessment were instantaneous readings the NPAAQS is a 24 hour average

CITY_21MC100_004151183

NYC-WTC_000295751

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295751Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →