COPCS report, NYC WTC chain of custody

Machine-extracted title · confidence 50%

Table of contents for contaminants of [name] report and building sections.

NYC-WTC_000276652–000276772
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

INTERNAL REVIEW DRAFT

0.01 f/cc. The TEM AHERA results indicate that two of the samples were below the detection limit and the third was at the detection limit with all three being below the secondary numeric criterion of 0.022 S/cc. The TEM PCMe results indicate that two of the samples were below the detection limit and the third was at the detection limit with all three being below the primary numeric criterion of 0.0009 S/cc.

Gypsum Before Cleaning Samples - There was one pre-cleaning wipe sample collected from the HVAC system. The results indicate gypsum was not detected above the detection limit lOmg/m^.

Post Cleaning Samples, HVAC System - There was one air sample and two wipe samples collected after the first cleaning. The results indicate that gypsum was not detected above the detection limit of 0.008 mg/nf for the air samples, and not detected above the detection limit of 10 mg/m^ for wipe samples.

Lead Before Cleaning Samples - There were one pre-cleaning wipe sample collected from the HVAC system. The results indicate lead was detected above the primary numeric criterion of 25 pg/lV at 1310 pg/ft^

Post P' Cleaning Samples, HVAC System - There were two air samples, and two wipe samples collected after the first cleaning. The two air samples were below the detection level and primary numeric criterion of 1 pg/m\ The results of the two wipe samples show that lead concentrations exceeded the numeric criterion at 136 pg/iV and 183 pg/f?. The post-cleaning lead exceedances were attributed to the composition of the HVAC construction material.

Post P' Cleaning Samples, Test 4A - There were five post cleanup air samples collected, all of which were below the detection level.

Alpha Quartz Before Cleaning Samples - There was one pre-cleaning wipe sample collected. The sample had alpha-quartz detected at a concentration of 313 mg/m\

Post Cleaning Samples, HVAC System - There were two wipe samples and one air sample collected after the first cleaning. The air sample was below the detection limit. Both wipe samples were above the detection limit. During the validation process, one wipe sample was qualified due to the duplicate being out of the control range.

97

CITY_21MC100_0 04205053

NYC-WTC_000276749

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000276749Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000243565

EIA report for Law Department project at 100 Church Street by TRC.

Similar indexed content

Compare copies and versions →