NYC 9/11 Public Portal Document
INTERNAL REVIEW DRAFT
Calcite
Before Cleaning Samples - There was one pre-cleaning wipe sample collected. The
sample had calcite detected above the detection limit.
Post J" Cleaning Samples, HVAC System - There was one air sample and two wipe
samples after the first cleaning. The air sample was below the detection limit, as well
as both wipe samples.
Cristobalite
Before Cleaning Samples - There was one pre-cleaning wipe sample collected. The
sample was below the detection limit.
Post P' Cleaning Samples, HVAC System - There was one air sample and two wipe
samples after the first cleaning. The air sample was below the detection limit, as well
as both wipe samples.
Tridymite
Before Cleaning Samples - There was one pre-cleaning wipe sample collected. The
sample was below the detection limit.
Post P' Cleaning Samples, HVAC System - There was one air sample and two wipe
samples after the first cleaning. The air sample was below the detection limit, as well
as both wipe samples.
MMVF
Before Cleaning Samples - There was one pre-cleaning wipe sample collected. The
wipe sample had an MMVF concentration of 11732.44 S/cc.
Post P' Cleaning Samples, HVAC System - There were three air samples and two
wipe samples collected after the first cleaning. All of the air and wipe sample results
indicate that MMVF concentrations were below the detection limit and the air
samples were below the primary numeric criterion of 10 S/L. This indicates that the
cleaning method was able to reduce the pre-cleaning concentration of MMVF in the
HVAC system.
Post Cleaning Samples, Test 4A - There were eight post-cleanup air samples
collected for MMVF. All sample concentrations were below the primary numeric
criteria of 10 S/L and six of the eight samples were below the detection limit.
Total Dust
Before Cleaning Samples - There were no pre-cleaning samples collected.