(basement) was used for food preparation and storage. The third level (sub-basement) was
used for storage of restaurant equipment. Ceramic tile covers the floor area in both the dining
room and the basement. The floor of the sub-basement is packed soil. All exterior windows
had been blown inward depositing significant amounts of dust on all surface areas of the first
floor. Minimal dust was present in the basement. The first floor ceiling by the Liberty Street
entrance is made of gypsum board. The ceiling on the Cedar Street entrance consists of
suspended acoustical tile covered with decorative tin facing. Above the suspended ceiling is
a two foot void space that houses the HVAC system for the establishment. The basement
ceiling is a suspended fibrous tile ceiling. The void space above both suspended ceilings and
the gypsum ceiling contained both WTC related and non-WTC related dust. Asbestos pipe
insulation was present in the void space of the basement. Grills, refrigerators, tables and
chairs were present on the first floor. The basement contains walk-in refrigerators,
preparation tables, stoves, dishwashing areas and dry goods storage. Prior to cleaning, all
open and bulk stored food, fibrous ceiling tiles in the basement, and wrap insulation that had
surrounded the HVAC systems were disposed.
Cleaning Method - This unit was cleaned using test method 4A and test method 4D.
Test method 4A used an industrial HEPA filtered vacuum and AFD. All horizontal
surfaces were wet wiped. For test method 4D, the HVAC system was cleaned by a
subcontractor utilizing standard industry cleaning techniques.
Numeric Criteria - This unit met the numeric criteria listed in Table 1 for each
compound after being cleaned one time.
Asbestos
Before cleaning samples - No pre-cleaning samples were collected from the restaurant
except one wipe sample and one bulk sample from the HVAC system. The wipe
sample concentration was below the detection limit. The bulk sample was analyzed
by PLM and found to contain <1% asbestos.
Post Cleaning Samples, Test 4A - Post-cleaning air samples were collected for
asbestos. The air samples were analyzed for PCM, TEM AHERA, and TEM PCMe.
The PCM results indicate that six of the samples were below the detection limit and
all eight samples were below the secondary numeric criterion of 0.01 f/cc. The TEM
AHERA results indicate that seven of the samples were below the detection limit and
all eight samples were below the numeric criterion of 0.022 S/cc. The TEM PCMe
results indicate that all eight of the air samples were below the detection limit and
below the primary numeric criterion of 0.0009 S/cc.
Post P' Cleaning, HVAC System - Post cleaning air and wipe samples were collected.
o
The air samples were analyzed for PCM, TEM AHERA, and TEM PCMe. The PCM
results indicate that all of the samples were below the secondary numeric criterion of
96