OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Lead (HVAC) Before Cleaning Samples - One wipe sample was collected. Lead was detected at a concentration above the primary clearance criterion of 25 pg/h^ with a value of 10700

Post P‘ Cleaning Samples - Four air samples were collected. All four samples were below the primary clearance criterion of 1.0 pg/m^. One of these samples was collected from the basement.

HVAC System - Three air samples and two wipe samples were collected after the HVAC system was cleaned. The air sample results indicate that all three air samples were below the detection limit. The two wipe sample results indicated that lead was still present at 25.9 pg/tv and 166 pg/tT. Both of these results were above the primary clearance criterion. Post cleaning lead exceedances were attributed to the composition of the HVAC construction material.

Alpha-Quartz (HVAC) Before Cleaning Samples - Pre-cleaning air samples were not collected.

Post P‘ Cleaning Samples - There were no samples collected after the first cleaning.

HVAC System - One air sample was collected. The air sample was below the detection limit.

Calcite Before Cleaning Samples - Pre-cleaning air samples were not collected.

Post P‘ Cleaning Samples - There were no samples collected after the first cleaning.

HVAC System - One air sample was collected after the HVAC system was cleaned. This sample was below the detection limit.

Cristobalite Before Cleaning Samples - Pre-cleaning air samples were not collected.

Post P' Cleaning Samples - There were no samples collected after the first cleaning.

HVAC System - One air sample was collected after the HVAC system was cleaned. This sample was below the detection limit.

Tridymite Before Cleaning Samples - Pre-cleaning air samples were not collected.

Post P‘ Cleaning Samples - There were no samples collected after the first cleaning.

HVAC System - One air sample was collected after the HVAC system was cleaned. This sample was below the detection limit.

94

CITY_21MC100_011063464

NYC-WTC_000363156

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000363156Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →