Cleaning method - This area was cleaned using test method 4A and test method 4B. Test
method 4A used an industrial HEPA filtered vacuum and an AFD, while test method 4B
consisted of a soap and water wet wipe of only the ceiling.
Numeric Criteria - This unit met the numeric criteria listed in Table 1 for each compound
after being cleaned once.
Asbestos
Before Cleaning Samples - There were no before cleaning samples collected.
Post P' Cleaning Samples - There was one post-cleaning air sample collected. The air
sample was analyzed using PCM, TEM AHERA, and TEM PCMe. The PCM result was
below the secondary numeric criterion of 0.01 f/cc. Similar ly, the TEM AHERA result was
below the secondary numeric criterion of 0.022 S/cc. The TEM PCMe result was below the
primary numeric criteria of 0.0009 S/cc with the sample being below the detection limit.
Dioxin
Before Cleaning Samples - There were no before cleaning samples collected.
Post P' Cleaning Samples - There were no post-first cleaning samples collected.
Gypsum
Before Cleaning Samples - There were no before cleaning samples collected.
Post P' Cleaning Samples - There was one air sample collected after the first cleaning. The
result indicates that gypsum was not detected.
Lead
Before Cleaning Samples - There were no before cleaning samples collected.
Post P' Cleaning Samples - There was one air sample collected after the first cleaning. The
air sample was below the numeric criterion of 1 pg/m^.
Alpha-Ouartz
Before Cleaning Samples - There were no before cleaning samples collected.
Post P' Cleaning Samples - There was one air sample collected after the first cleaning. The
sample was below the detection limit.
Calcite
Before Cleaning Samples - There were no before cleaning samples collected.