HEP A filtered vacuum and an AFD. Test 4B was a soap and water wet wipe of the ceiling and floor only.

Cleaning Results - This unit met the clearance criteria listed in Table 1.0 for each compound after being cleaned once.

Asbestos Before Cleaning Samples - There were no pre-cleaning samples collected.

Post P’ Cleaning Samples - Two post-cleaning air samples were collected. The two air samples were analyzed using PCM, TEM AHERA, and PCMe. The PCM results were all below the secondary numeric criterion of 0.01 f7cc. Similarly, the TEM AHERA results were all below the secondary numeric criterion of 0.022 S/cc. The PCMe results were all below the primary clearance criterion of 0.0009 S/cc with one of the two samples being below the detection limit.

Dioxin Before Cleaning Samples - There were no pre-cleaning samples collected.

Post P‘ Cleaning Samples - There were no post-cleaning samples collected

Gypsum Before Cleaning Samples - There were no pre-cleaning samples collected.

Post P‘ Cleaning Samples - Two air samples were collected after the first cleaning. Gypsum was not detected in any sample.

Le^ Before Cleaning Samples - There were no pre-cleaning samples collected.

Post P‘ Cleaning Samples - Two air samples were collected after the first cleaning. The two air samples were below the detection limit.

Alpha-Quartz Before Cleaning Samples - There were no pre-cleaning samples collected.

Post P‘ Cleaning Samples - Two air samples were collected after the first cleaning. All of the samples were below the detection limit.

Calcite Before Cleaning Samples - There were no pre-cleaning samples collected.

Post P‘ Cleaning Samples - Two air samples were collected after the first cleaning. Both were below the detection limit.

Cristobalite Before Cleaning Samples - There were no pre-cleaning samples collected.

44

CITY_21MC100_011105274

NYC-WTC_000195240

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000195240Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →