and TEM PCMe. The PCM results indicate that one sample was below the secondary
numeric criterion and the other two could not be analyzed due to particulate overloading of
the filter. The TEM AHERA results were below the secondary numeric criterion for two
samples. The third sample could not be analyzed due to particulate overloading of the filter.
Of the three air samples analyzed using TEM PCMe, one sample could not be analyzed due
to overloading of particulate material and the other two samples were below the primary
numeric criteria of 0.0009 S/cc.
The results of the four micro vacuum samples indicate that asbestos was present at levels
generally lower than those observed before cleaning, and one of the samples was identified as
non-detect.
The results of the five wipe samples indicate that asbestos was present in three samples. The
other two samples were identified as non-detect. One of the non-detect samples had an
elevated detection limit due to the presence of non-asbestos particulate matter.
Dioxin
Before Cleaning Samples - There were three pre-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that there was dioxin present; however, the TEQ
concentrations for each sample were below the numeric criterion of 4 ng/'mf
Post Cleaning Samples - There were four post-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that the concentrations of dioxin detected were
similar to the pre-cleaning samples and the TEQ concentrations for each sample were below
the criterion of 4 nghnY
Gypsum
Before Cleaning Samples - There were three pre-cleaning wipe samples collected. The
results indicate gypsum was not detected above the detection limit. It should be noted that
the detection limit ranged from 1 to 10 mg/m^.
Post P' Cleaning Samples - There were two air samples and four wipe samples collected after
the first cleaning. The results indicate that gypsum was not detected above the detection limit
for the air samples, and not detected above the detection limit for wipe samples.
Lead
Before Cleaning Samples - There were four micro vacuum samples and three wipe samples
collected. The results indicate that lead was not detected in any of the micro vacuum
samples. One of the wipe samples was below the detection limit and one wipe sample was
below primary numeric criteria of 25 pg/ftf The third wipe sample exceeded the primary
numeric criteria at 38.9 pg/fF.