contamination. Equipment used in these units ranged from basic vacuums to
the more advance industrial vacuums in combination with Air Filtration
Devices (AFD).
Six units met the numeric criteria after two cleanings (2A, 3B, 3D, 4A, 5A).
These units had both high and low average levels of contamination.
Equipment used in these units ranged from basic vacuums to the more
advance industrial vacuums in combination with AFDs. One of these units
included wet wiping of all surfaces.
Two units (3C, 5C) failed to meet the numeric criteria after two cleaning
events utilizing the equipment specified. These units both were in the top half
of the units in terms of average concentration of contamination. One unit used
advance equipment, the other basic equipment with wet wiping of all surfaces.
These units met the numeric criteria only after performing the third cleaning
with advanced industrial vacuums in combination with AFDs.
Table 11, Contaminant Removal Efficiency After the First Cleaning Event of
Units Identified Through Pre-Cleaning Measurements as Most Contaminated
(2A, 2B, 3C, 3D, 4C, 4D, 5A and 5C), demonstrates that all methods were
fairly successful in removing significant amounts of contaminants through the
first cleaning.
Generally, there was a reduction in the level of contamination from one cleaning to
the next regardless of the type of cleaning method used.
• Table 12, Pre- and Post-Cleaning Levels of Average Contamination,
demonstrate the levels of reduction.
Generally, all methods were extremely effective in reducing lead (wipe and micro
vacuum averages) and MMVF (wipe averages) dust concentrations after one cleaning
regardless of the level of contamination at the start of cleaning.
• Reductions were to levels of comparison to clearance in 11 of the 13 cases.
See Table 4 for more details.
Overall, all methods were able to clean to levels that met clearance criteria although
some required multiple cleanings.
• There were two exceptions; unit 3C was cleaned twice using test lA needed to
use 3B to achieve clearance, and unit 5C was cleaned twice using test 3A
needed to use test 3B .
Overall, clearance based on PCMe results is an extremely conservative methodology
to use to determine if further cleaning is warranted. Additionally, PCMe provides a
good indicator for other compounds.
• It was necessary to reclean eleven times (9 second cleanings and 2 third
cleanings) and 9 out of the eleven recleanings (82%) were conducted primarily