The ASTM method is intended for guidance on examining dust coniamination of building
surfaces and. is intended as a general assessment of the building. There is no suggestion
in the ASTM method that it can be u.sed to assess geneial health risk from asbestos
exposure, nor does it suggest that all building surfaces be maintained to the levels
published in tire standard. The method is generally applicable for the estimate of the
concentration of asbestos fibers on surfaces starting from approximately 1000 fibers per
square centimeter (f/cm2)
On December 3"“ two surface dust samples were taken from the 10* floor to determine
whether asbestos fibers were settled on surfaces. The results are rejported in asbestos
fibers per square centimeter of surface tested. The following summarizes the sample
results:
Sample C620204 sampled in living room from table top
Result- 740 asbestos structures per square centimeter
Sample E1203-2 sampled from supply air diffuser in the 10* floor public hallway
Result - 550,000 asbestos structures per square centimeter
The supply air grille in the hallway was found to have elevated levels of asbestos fibers
well above the recommended limit of 1000 structures per square centimeter. This
suggests that the ventilation system was contaminated by asbestos when the building
collapsed.
The duct system should be cleaned by a professional duct cleaning company using
vacuum and cleaning equipment designed for asbestos decontamination.
Sincerely,
Edward Olmsted