Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗ATC IAQ report for 90 Trinity Place, measurements collected April 9, 2002, BOE program.
NYC-WTC_000260070–000260073OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Oilan April 10, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Env]ironmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 10:45 A.M. and concluded after 1:50 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.3 °F to 77.5 °F. One hundred and ten (110) indoor measurements for temperature were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 68.5 °F to 73.4 °F.
Relative Humidity
The relative humidity indoors ranged from 42.2 percent to 52.9 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 40.9 to 49.2 percent.
CarbonDioxia'e Concentration
Carbon dioxide concentrations indoors ranged from 419 ppm to 1410 ppm. Two (2) the indoor measurements for CO2 were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 422 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1122 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. Tlie primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm- 4 ppm.
Respirable Particulates (PM2,5)
Respirable paniculate concentrations* indoors ranged between 2 pg/m^ to 36 pg/m^ with an average 6 pg/m^. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 36 pg/m^ to 54 pgmU with an average of 43 pg/m3. Six (6) of the twelve (12) instantaneous outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
CONFIDENTIAL, CITY_21MC100_003463858 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260072
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260056
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189397
Report of indoor air quality measurements collected at a school on April 9, 2002, to determine if acceptable air quality is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260303
May 8, 2002; IAQ measurements requested by BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260108
ATC IAQ measurements collected April 16, 2002 at the referenced school under BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260469
ATC provides indoor air quality measurements collected May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296855
ATC IAQ measurements report for 90 Trinity Place; dated Apr 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260537
ATC IAQ measurements collected June 7, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260451
Indoor air quality measurements taken May 22, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000394791
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377102
Memobrief/letter reporting IAQ measurements at a NYC high school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260052
ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189397
Report of indoor air quality measurements collected at a school on April 9, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211859
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
NYC-WTC_000260056
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 25, 2002.
Similar indexed content
NYC-WTC_000189397
Report of indoor air quality measurements collected at a school on April 9, 2002, to determine if acceptable air quality is maintained.
Similar indexed content
May 8, 2002; IAQ measurements requested by BOE.
Similar indexed content
NYC-WTC_000260108
ATC IAQ measurements collected April 16, 2002 at the referenced school under BOE request.
Similar indexed content