Mr. Bernard P. Orlan April 22, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894~) ATC Project No. 15-19125-0290 Real-Time Environiviental Measurements

ATC collected one hundred and thirty-eight (138) sets of real-time environmental measurements consisting of one hundred and twenty six (126) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 84°F to 88.9°F. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature range was 82.4 °F to 88.5 °F.

Relative Humidity

The relative humidity indoors ranged from 36 percent to 45.3 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 36,1 to 45.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 439 ppm to 1050 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 932 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1632 ppm (background level -t 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Particulates (PM2 ,5)

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 25 pg/m3 with an average 18 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 11 pg/m^ to 52 pg/m^ with an average of 24 ug/m^. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) of the twelve (12) instantaneous readings were above, USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children.

CITY_21MC100_002918675

NYC-WTC_000394793

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394793Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000399254

Indoor air quality report dated May 7, 2002 for High School project; ATC.

Similar indexed content

Compare copies and versions →