Mr. Bernard P. Orlan ■April 26, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements ■ consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 7:32 Am and concluded at 3:58 PM. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 67.9 °F to 75.1 °F. Ninety-four (94) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). The outdoor temperature ranged from 57.7 to 67.3 °F.'

Relative Humidity

The relative humidity indoors ranged from 31.0 percent to 49.4 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 29.7 to 41.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 617 ppm to 1232 ppm. One (1) of the indoor . measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 428 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1128 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from Ippm to 3ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from Ippm to 2ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 21 pg/m^ with an average 10 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All measurements were also below than the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 21 pg/m^ to 52 pg/m^ with an average of 35pg/m3. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter, and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

CITY_21MC100_002918750

NYC-WTC_000394852

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394852Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394734

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000291988

ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.

Similar indexed content

Compare copies and versions →